Altronix T2MK7716 kit consists of Trove2 enclosure, TM2 Altronix and Mercury backplane and TMV2 door backplane with two 24 VDC at 10 A power supply/chargers, 12 VDC voltage regulator, eight fuse protected output dual voltage power distribution module and two eight fuse protected output access control modules. This kit also accommodates various combinations of Mercury boards for up to sixteen doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.
Also compatible with these authentic Mercury partners: AccessNsite, Avigilon, BadgePass, BluBox, Feenics, Genetec, Identicard, IMRON, Johnson Controls, Kastle, Keri Systems, Lenel/S2, LockState, Maxxess, Midpoint Security, NLSS, Open Options, Panasonic Video Insight, Quintron, RS2, Schneider Electric, Vanderbilt.
Features
Two AL1024ULXB2 Power Supply/Charger
- Input
- Voltage: 115 VAC 60 Hz, 4.2 A max
- Main Fuse: 5 A/250 V
- Outputs
- Voltage: 24 VDC
- Current: 10 A at 24 VDC continuous max
- Other: Overvoltage protection. Filtered and regulated
- Battery Backup (not included)
- Capacity: 12 AH/12 VDC (2 within enclosure), 40 AH / 65 AH (requires separate enclosure)
- Type: Sealed lead acid or gel type
- Failover: Upon AC loss, instantaneous
- Supervision
- AC Failure: Form C contacts
- Battery: Form C contacts
- Indicators LED
- Input: 115 VAC is present
- DC Output: Powered
- Battery: Discharged or not connected
PDS8 Dual Input Power Distribution Module
- Input
- Voltage: 12 VDC from VR6 and 24 VDC from AL1024ULXB2
- Input Fuse: 10 A/32 V
- Outputs
- Voltage: 12 and/or 24VDC
- Any of the eight power outputs are selectable to follow power Input 1 or Input 2
- Individual outputs may be set to OFF position for servicing
- Outputs Ratings Fuses: 3 A/32 V
- Indicators LED
- DC Output: Eight individual output LEDs
- Green: 12 VDC
- Red: 24 VDC
VR6 Voltage Regulator
- Input
- Voltage: 24 VDC from AL1024ULXB2
- Output
- Voltage: 12 VDC
- Current: 6 A continuous
- Other: Surge suppression
- Indicators LED
- Input: 24 VDC is present
- Output: Powered
Two ACM8 Access Power Controllers
- Input
- Voltage: 24 VDC from AL1024ULXB2
- Input Fuse: 10 A/250V
- Outputs
- Voltage: 24 VDC
- Eight independently controlled fused outputs:
a) Fail-Safe and/or Fail-Secure power outputs. Form C Relays rated 28 VAC or VDC at 2.5A.
b) Auxiliary power outputs (unswitched).
c) Any combination of the above
- Output Fuses: 3.5 A/250 V
- Indicators (LED)
- Red LEDs: Outputs are triggered (relays energized)
- Green LED: FACP disconnect is triggered
Environmental
- Temperature
- Operating: 0° C to 49° C (32° F to 120° F)
- Storage: - 20° C to 70° C ( - 4° F to 158° F)
- Relative Humidity
- Relative Humidity 85% +/- 5%
- BTU/Hr (approx.):
- 289 BTU/Hr