
Potter CPS-24 Conventional Photoelectric Smoke Detector
Potter CPS-24 Conventional Photoelectric Smoke Detector
- Suitable for in-duct applications
- 360° view of detector status LED
- Low profile, 2" high ( with base)
- Suitable for in-duct applications
- 360° view of detector status LED
- Low profile, 2" high ( with base)
Sign In for Dealer Pricing
Become an ADI Customer- Suitable for in-duct applications
- 360° view of detector status LED
- Low profile, 2" high ( with base)

Please sign in to view pricing and availability and to add to cart.
Accessories
Product Overview
The CPS-24 photoelectric smoke detector utilizes one bicolored LED for indication of status. In a normal standby condition the LED flash Green every 3 seconds. When the detector senses that its sensitivity has drifted outside the UL listed sensitivity window the LED will flash Red every 3 seconds. When the detector senses smoke and goes into alarm the status LED will latch on Red.
The detector utilizes an infrared LED light source and silicon photodiode receiving element in the smoke chamber. In a normal standby condition, the receiving element receives no light from the pulsing LED light source. In the event of a fire, smoke enters the detector smoke chamber and light is reflected from the smoke particles to the receiving element. The light received is converted into an electronic signal.
Fire Judgement signals are processed and compared to a reference level, and when five consecutive signals exceeding the reference level are received within a specified period of time, the time delay circuit triggers the SCR switch to activate the alarm signal. The status LED lights continuously during the alarm period.
Main Features
- Suitable for in-duct applications
- 360° view of detector status LED
- Low profile, 2" high ( with base)
- 2 or 4 wire base compatibility, relay bases available
- Highly stable operation, RF/Transient protection
- Low standby current, 59µA at 24VDC
- One built-in power/sensitivity supervision/alarm LED
- Automatic Sensitivity window verification function meets outlined requirements in NFPA 72, Chapter 2 & 7, Inspection, Testing and Maintenance.
- Magnetic Test Feature
General Information
Specifications
-
ADI Part Number PL-CPS24 Brand Name Potter Electric Signal, LLC Manufacturer Potter Electric Signal, LLC Manufacturer Part Number CPS-24 Product Line Conventional Product Model CPS-24 Product Name Conventional Photoelectric Smoke Detector Product Type Smoke Detector Weight 1lb
-
Connectivity Technology Wired Detectable Medium Fire Sensing Technology Photoelectric Sensor Type Photoelectric, Thermal
-
UL Listed Yes
-
Status Indicators Alarm, LED
-
Color White Form Factor Ceiling Mount
-
Input Voltage 24V DC
-
Certifications UL 268 Compatibility Fire Alarm Panel Country of Origin US